YTCC comes with 25 ready signal types in the Product library. Each type defines the signals of one piece of equipment (its elements), their data types, units, alarms and archives, and address templates for the protocols listed. Parameters such as the base register or the first information object address are entered when you create an instance; see Signal types and instances and Use the type library.

In the tables, Alarm shows the priority of a state alarm or the levels of a limit alarm; (off) means the alarm is defined but switched off in the type. The library texts are in English.

Process​

Air compressor​

Running, loaded, fault and auto status, start / stop commands with feedback, discharge pressure and temperature, running and loaded hours.

Name: Compressor · 10 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
runningBoolread——Running
loadedBoolread——Loaded
faultBoolread—HighCompressor fault
autoBool (AutoManual)read——Auto mode
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
discharge_pressureFloat32readbarH (off)Discharge pressure
discharge_tempFloat32read°CH/HHDischarge temperature
run_hoursFloat32readh—Running hours
load_hoursFloat32readh—Loaded hours

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Flow meter​

Flow rate with prepared (inactive) limits and totalised volume.

Name: FlowMeter · 2 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA, DNP3

ElementData typeAccessUnitAlarmDescription
flowFloat32readm³/hLL/L/H/HH (off)Flow
totalFloat64readm³—Totalised volume

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2
aiDNP3 index of the first analog input0
cntDNP3 counter index of the first counter0

Pressure transmitter​

Single pressure measurement with prepared (inactive) limits.

Name: PressureTransmitter · 1 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA, DNP3

ElementData typeAccessUnitAlarmDescription
``Float32readbarLL/L/H/HH (off)Pressure

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2
aiDNP3 index of the first analog input0

Pump (direct on line)​

Running, fault, auto and dry-running status, start / stop commands with feedback, discharge pressure, running hours and start counter.

Name: Pump · 9 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
runningBoolread——Running
faultBoolread—HighPump fault
autoBool (AutoManual)read——Auto mode
dry_runBoolread—HighDry running
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
discharge_pressureFloat32readbarL/H (off)Discharge pressure
run_hoursFloat32readh—Running hours
startsUInt32read——Number of starts

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Tank / reservoir level​

Level, level in percent, volume and level switches. Level alarms are prepared but inactive; set them for the tank geometry.

Name: TankLevel · 5 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
levelFloat32readmLL/L/H/HH (off)Level
level_pctFloat32read%—Level in percent
volumeFloat32readm³—Volume
high_switchBoolread—HighHigh level switch
low_switchBoolread—HighLow level switch

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Temperature transmitter​

Single temperature measurement with prepared (inactive) limits.

Name: TemperatureTransmitter · 1 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA, DNP3

ElementData typeAccessUnitAlarmDescription
``Float32read°CLL/L/H/HH (off)Temperature

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2
aiDNP3 index of the first analog input0

Motors​

Motor (direct on line)​

Running, fault, overload and auto status, start / stop commands with feedback, current, running hours and start counter.

Name: MotorDOL · 9 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
runningBoolread——Running
faultBoolread—HighMotor fault
overload_tripBoolread—HighOverload trip
autoBool (AutoManual)read——Auto mode
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
currentFloat32readA—Motor current
run_hoursFloat32readh—Running hours
startsUInt32read——Number of starts

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Motor with frequency converter​

Running, fault and auto status, start / stop / reset commands, speed setpoint and actual speed, output frequency, current, power, DC bus voltage, fault code and running hours.

Name: MotorVFD · 14 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
runningBoolread——Running
faultBoolread—HighDrive fault
autoBool (AutoManual)read——Auto mode
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
reset_cmdBoolwrite——Fault reset command
speed_setpointFloat32read/write%—Speed setpoint
speed_actualFloat32read%—Actual speed
output_frequencyFloat32readHz—Output frequency
motor_currentFloat32readA—Motor current
motor_powerFloat32readkW—Motor power
dc_bus_voltageFloat32readV—DC bus voltage
fault_codeUInt16read——Fault code
run_hoursFloat32readh—Running hours

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Valves​

Modulating valve​

Position feedback and setpoint, valve fault and auto mode.

Name: ValveModulating · 4 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
positionFloat32read%—Valve position
position_setpointFloat32read/write%—Valve position setpoint
faultBoolread—MediumValve fault
autoBool (AutoManual)read——Auto mode

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

On/off valve​

Opened / closed limit switches, open / close commands with feedback, travel fault and auto mode.

Name: ValveOnOff · 6 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
openedBoolread——Opened
closedBoolread——Closed
open_cmdBoolwrite——Open command
close_cmdBoolwrite——Close command
faultBoolread—MediumValve travel fault
autoBool (AutoManual)read——Auto mode

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

HVAC​

Air handling unit​

Enable command, running and fan status, fan / filter / frost alarms, supply and return air temperature, supply setpoint, heating and cooling valves and damper position.

Name: AHU · 14 elements · Protocols: Modbus, OPC UA, BACnet

ElementData typeAccessUnitAlarmDescription
enable_cmdBoolread/write——Enable command
runningBoolread——Running
autoBool (AutoManual)read——Auto mode
supply_fan_runningBoolread——Supply fan running
exhaust_fan_runningBoolread——Exhaust fan running
fan_faultBoolread—HighFan fault
filter_dirtyBoolread—LowFilter dirty
frost_alarmBoolread—HighFrost protection
supply_tempFloat32read°C—Supply air temperature
return_tempFloat32read°C—Return air temperature
supply_temp_setpointFloat32read/write°C—Supply air temperature setpoint
heating_valveFloat32read%—Heating valve position
cooling_valveFloat32read%—Cooling valve position
damper_posFloat32read%—Damper position

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
nsOPC UA namespace index2
biBACnet instance of the first binary input0
aiBACnet instance of the first analog input0
aoBACnet analog output instance of the first output0
avBACnet analog value instance of the first value0
bvBACnet binary value instance of the first value0

Fan (direct on line)​

Running, fault and auto status, start / stop commands with feedback and running hours.

Name: Fan · 6 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
runningBoolread——Running
faultBoolread—HighFan fault
autoBool (AutoManual)read——Auto mode
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
run_hoursFloat32readh—Running hours

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Safety​

Door contact​

Single door contact with a door open alarm.

Name: DoorAlarm · 1 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
``Bool (DoorState)read—LowDoor contact

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Fire alarm zone​

Fire, zone fault and zone disabled status.

Name: FireAlarmZone · 3 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
fireBoolread—CriticalFire
faultBoolread—MediumFire zone fault
disabledBoolread——Zone disabled

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Switchgear​

Circuit breaker (IEC double point)​

Double-point position with separate intermediate and faulty bits, open / close commands with select-before-operate and position feedback, protection and supply alarms, operation counter.

Name: CircuitBreaker · 15 elements · Protocols: IEC 104, IEC 101, OPC UA, DNP3

ElementData typeAccessUnitAlarmDescription
posEnum (DoublePoint)read——Position
pos_intermediateBoolread—MediumIntermediate position
pos_faultyBoolread—HighFaulty position
open_cmdBoolwrite——Open command
close_cmdBoolwrite——Close command
localBool (LocalRemote)read——Local control
interlockedBoolread——Interlocked
close_blockedBoolread——Close blocked
protection_tripBoolread—HighProtection trip
relay_faultBoolread—HighProtection relay fault
dc_supply_failBoolread—HighControl DC supply lost
mcb_trippedBoolread—MediumMCB tripped
sf6_lowBoolread—HighSF6 pressure low
operationsUInt32read——Operation counter
currentFloat32readA—Current

Parameters:

ParameterMeaningDefault
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2
dbiDNP3 double-bit input index of the first element0
biDNP3 index of the first binary input0
boDNP3 binary output index of the first command0
aiDNP3 index of the first analog input0
cntDNP3 counter index of the first counter0

Circuit breaker (PLC single bits)​

Breaker and disconnector position bits, outputs, lock and open / close commands in an 8-byte PLC block.

Name: CircuitBreakerPlc · 12 elements · Protocols: Modbus, S7, OPC UA

ElementData typeAccessUnitAlarmDescription
openedBoolread——Opened
closedBoolread——Closed
open_outputBoolread——Open output active
close_outputBoolread——Close output active
disc_openedBoolread——Disconnector opened
disc_closedBoolread——Disconnector closed
lockedBoolread——Locked
open_cmdBoolread/write——Open command
close_cmdBoolread/write——Close command
open_timerUInt16reads—Open timer
close_timerUInt16reads—Close timer
lock_wordUInt16read——Lock word

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
nsOPC UA namespace index2

Disconnector (IEC double point)​

Double-point position with separate intermediate and faulty bits, open / close commands with select-before-operate and position feedback, operation counter.

Name: Disconnector · 9 elements · Protocols: IEC 104, IEC 101, OPC UA, DNP3

ElementData typeAccessUnitAlarmDescription
posEnum (DoublePoint)read——Position
pos_intermediateBoolread—MediumIntermediate position
pos_faultyBoolread—HighFaulty position
open_cmdBoolwrite——Open command
close_cmdBoolwrite——Close command
localBool (LocalRemote)read——Local control
interlockedBoolread——Interlocked
mcb_trippedBoolread—MediumMotor supply MCB tripped
operationsUInt32read——Operation counter

Parameters:

ParameterMeaningDefault
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2
dbiDNP3 double-bit input index of the first element0
biDNP3 index of the first binary input0
boDNP3 binary output index of the first command0
cntDNP3 counter index of the first counter0

Protection​

Feeder protection relay​

Currents, voltages, power, power factor, frequency, fault distance, protection trips, relay healthy status and auto-reclose counter.

Name: ProtectionRelay · 18 elements · Protocols: IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
i_l1Float32readA—Current L1
i_l2Float32readA—Current L2
i_l3Float32readA—Current L3
i_nFloat32readA—Neutral current
u_l1_l2Float32readkV—Voltage L1-L2
u_l2_l3Float32readkV—Voltage L2-L3
u_l3_l1Float32readkV—Voltage L3-L1
pFloat32readMW—Active power
qFloat32readMvar—Reactive power
pfFloat32read——Power factor
frequencyFloat32readHz—Frequency
fault_distanceFloat32readkm—Fault distance
tripBoolread—HighProtection trip
earth_fault_tripBoolread—HighEarth fault trip
overcurrent_tripBoolread—HighOvercurrent trip
distance_tripBoolread—HighDistance protection trip
healthyBoolread——Relay healthy
reclose_countUInt32read——Auto-reclose counter

Parameters:

ParameterMeaningDefault
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Transformers​

Power transformer​

Oil and winding temperatures, tap position and raise / lower commands, Buchholz, temperature, oil level, pressure relief and protection trips.

Name: PowerTransformer · 17 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
oil_tempFloat32read°CH/HHOil temperature
winding_tempFloat32read°CH/HHWinding temperature
tap_posInt16read——Tap position
tap_raise_cmdBoolwrite——Tap raise command
tap_lower_cmdBoolwrite——Tap lower command
buchholz_alarmBoolread—HighBuchholz alarm
buchholz_tripBoolread—CriticalBuchholz trip
oil_temp_alarmBoolread—MediumOil temperature alarm
oil_temp_tripBoolread—HighOil temperature trip
winding_temp_alarmBoolread—MediumWinding temperature alarm
winding_temp_tripBoolread—HighWinding temperature trip
oil_level_lowBoolread—MediumOil level low
oil_level_highBoolread—LowOil level high
pressure_relief_tripBoolread—CriticalPressure relief trip
tap_changer_tripBoolread—HighTap changer protection trip
differential_tripBoolread—CriticalDifferential protection trip
overcurrent_tripBoolread—HighOvercurrent trip

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Generation​

Synchronous generator​

Power, voltage, current, speed, stator and bearing temperatures, excitation, state, trip, P / Q setpoints, start / stop commands and running hours. Ranges suit units up to 20 MVA; adjust on site.

Name: Generator · 26 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
p_activeFloat32readkW—Active power
q_reactiveFloat32readkvar—Reactive power
s_apparentFloat32readkVA—Apparent power
pfFloat32read——Power factor
frequencyFloat32readHz—Frequency
u_abFloat32readkV—Voltage A-B
u_bcFloat32readkV—Voltage B-C
u_caFloat32readkV—Voltage C-A
i_aFloat32readA—Current A
i_bFloat32readA—Current B
i_cFloat32readA—Current C
speedFloat32readrpm—Speed
stator_temp_uFloat32read°CH/HHStator temperature U
stator_temp_vFloat32read°CH/HHStator temperature V
stator_temp_wFloat32read°CH/HHStator temperature W
bearing_de_tempFloat32read°CH/HHBearing temperature, drive end
bearing_nde_tempFloat32read°CH/HHBearing temperature, non-drive end
excitation_currentFloat32readA—Excitation current
excitation_voltageFloat32readV—Excitation voltage
stateEnum (RunState)read——Operating state
tripBoolread—CriticalGenerator trip
p_setpointFloat32read/writekW—Active power setpoint
q_setpointFloat32read/writekvar—Reactive power setpoint
start_cmdBoolwrite——Start command
stop_cmdBoolwrite——Stop command
running_hoursFloat64readh—Running hours

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Hydro turbine (Pelton / Francis)​

Speed, guide vane or nozzle opening and setpoint, inlet pressure, net head, HPU oil pressure, state and shutdown alarms. Add nozzle_<n>_pos elements per site.

Name: HydroTurbine · 9 elements · Protocols: IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
speedFloat32read%—Turbine speed
guide_posFloat32read%—Guide vane / nozzle opening
guide_setpointFloat32read/write%—Guide vane / nozzle opening setpoint
inlet_pressureFloat32readbarLL/L/H/HH (off)Inlet pressure
net_headFloat32readm—Net head
hpu_oil_pressureFloat32readbarLL/L (off)HPU oil pressure
stateEnum (RunState)read——Operating state
emergency_shutdownBoolread—CriticalEmergency shutdown
hpu_faultBoolread—HighHPU fault

Parameters:

ParameterMeaningDefault
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Energy​

Generic energy analyser​

Phase voltages and currents, total P, Q, S, power factor, frequency and energy totals. For medium voltage change the voltage unit to kV on the signal.

Name: EnergyAnalyser · 18 elements · Protocols: Modbus, S7, IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
u_l1_nFloat32readV—Voltage L1-N
u_l2_nFloat32readV—Voltage L2-N
u_l3_nFloat32readV—Voltage L3-N
u_l1_l2Float32readV—Voltage L1-L2
u_l2_l3Float32readV—Voltage L2-L3
u_l3_l1Float32readV—Voltage L3-L1
i_l1Float32readA—Current L1
i_l2Float32readA—Current L2
i_l3Float32readA—Current L3
p_totalFloat32readkW—Total active power
q_totalFloat32readkvar—Total reactive power
s_totalFloat32readkVA—Total apparent power
pf_totalFloat32read——Total power factor
frequencyFloat32readHzL/HFrequency
energy_import_activeFloat64readkWh—Active energy import
energy_export_activeFloat64readkWh—Active energy export
energy_import_reactiveFloat64readkvarh—Reactive energy import
energy_export_reactiveFloat64readkvarh—Reactive energy export

Parameters:

ParameterMeaningDefault
modbus_baseModbus base register of the instance (1-based)1
unit_idModbus unit id1
dbS7 data block number1
offByte offset of the instance in the data block0
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

Energy analyser (Siemens SENTRON PAC3220)​

U, I, P, Q, S, power factor, THD, frequency and energy counters over Modbus TCP (35 float32 + 10 float64).

Name: PAC3220 · 45 elements · Protocols: Modbus

ElementData typeAccessUnitAlarmDescription
voltage_L1_NFloat32readVL/HVoltage L1-N
voltage_L2_NFloat32readVL/HVoltage L2-N
voltage_L3_NFloat32readVL/HVoltage L3-N
voltage_L1_L2Float32readVL/HVoltage L1-L2
voltage_L2_L3Float32readVL/HVoltage L2-L3
voltage_L3_L1Float32readVL/HVoltage L3-L1
current_L1Float32readA—Current L1
current_L2Float32readA—Current L2
current_L3Float32readA—Current L3
apparent_power_L1Float32readVA—Apparent power L1
apparent_power_L2Float32readVA—Apparent power L2
apparent_power_L3Float32readVA—Apparent power L3
active_power_L1Float32readW—Active power L1
active_power_L2Float32readW—Active power L2
active_power_L3Float32readW—Active power L3
reactive_power_L1Float32readvar—Reactive power L1
reactive_power_L2Float32readvar—Reactive power L2
reactive_power_L3Float32readvar—Reactive power L3
power_factor_L1Float32read——Power factor L1
power_factor_L2Float32read——Power factor L2
power_factor_L3Float32read——Power factor L3
thd_voltage_L1Float32read%HVoltage THD L1
thd_voltage_L2Float32read%HVoltage THD L2
thd_voltage_L3Float32read%HVoltage THD L3
thd_current_L1Float32read%—Current THD L1
thd_current_L2Float32read%—Current THD L2
thd_current_L3Float32read%—Current THD L3
frequencyFloat32readHzL/HFrequency
voltage_avg_L_NFloat32readVL/HAverage voltage L-N
voltage_avg_L_LFloat32readVL/HAverage voltage L-L
current_avgFloat32readA—Average current
apparent_power_totalFloat32readVA—Total apparent power
active_power_totalFloat32readW—Total active power
reactive_power_totalFloat32readvar—Total reactive power
power_factor_totalFloat32read——Total power factor
active_energy_import_t1Float64readWh—Active energy import, tariff 1
active_energy_import_t2Float64readWh—Active energy import, tariff 2
active_energy_export_t1Float64readWh—Active energy export, tariff 1
active_energy_export_t2Float64readWh—Active energy export, tariff 2
reactive_energy_import_t1Float64readvarh—Reactive energy import, tariff 1
reactive_energy_import_t2Float64readvarh—Reactive energy import, tariff 2
reactive_energy_export_t1Float64readvarh—Reactive energy export, tariff 1
reactive_energy_export_t2Float64readvarh—Reactive energy export, tariff 2
apparent_energy_t1Float64readVAh—Apparent energy, tariff 1
apparent_energy_t2Float64readVAh—Apparent energy, tariff 2

Parameters:

ParameterMeaningDefault
modbus_baseModbus base address (device has no register 0)2
unit_idModbus unit id1

Auxiliary​

Station DC supply (rectifier + battery)​

DC voltage and DC system alarms. The low-voltage limit is set for a 110 V system; change it on 48 V systems.

Name: DcSystem · 6 elements · Protocols: IEC 104, IEC 101, OPC UA

ElementData typeAccessUnitAlarmDescription
dc_voltageFloat32readVLDC voltage
dc_low_voltageBoolread—HighDC voltage low
rectifier_faultBoolread—HighRectifier fault
earth_faultBoolread—MediumDC earth leakage
ac_supply_lostBoolread—HighAC supply lost
main_breaker_offBoolread—MediumDC main breaker off

Parameters:

ParameterMeaningDefault
ioaInformation object address of the first element (IEC 104 / IEC 101)1
nsOPC UA namespace index2

UPS​

Uninterruptible power supply (SNMP UPS-MIB)​

Output source, battery status, charge, runtime and temperature, input / output voltage, input frequency, load and alarm count from the standard UPS-MIB (RFC 1628).

Name: UPS · 10 elements · Protocols: OPC UA, SNMP

ElementData typeAccessUnitAlarmDescription
output_sourceEnum (UpsOutputSource)read——Output source
battery_statusEnum (UpsBatteryStatus)read——Battery status
battery_chargeFloat32read%L/LLBattery charge remaining
battery_runtimeFloat32readminLEstimated runtime on battery
battery_tempFloat32read°CHBattery temperature
input_voltageFloat32readV—Input voltage
input_frequencyFloat32readHz—Input frequency
output_voltageFloat32readV—Output voltage
output_loadFloat32read%H/HHOutput load
alarms_presentUInt32read—HActive UPS alarms

Parameters:

ParameterMeaningDefault
nsOPC UA namespace index2