Skip to main content

Voltage levels, sources and palette

The colors of a single-line diagram come from two project tables: the voltage levels (color, nominal voltage and measurement thresholds) and the sources (which network feeds a section). They are the same on every page, so a color always means the same thing to the operator. For how the colors are worked out, see How the live single-line diagram works.

Before you begin​

Steps​

1. Open the electrical settings​

Click an empty place on the canvas. In PROPERTIES, scroll to ELECTRICAL › COLORING.

ELECTRICAL › COLORING settings with Automatic coloring, Coloring source, Palette, Two different sources, Secured supply, De-energized color and Join warning.
SettingDefaultMeaning
Automatic coloringonOff: symbols keep their design color. Interlocks, warnings and the ? mark still work.
Coloring sourceServer (recommended)Where the states are calculated; see Where the colors are calculated.
PaletteClassic (voltage level colors)ISA-101 (normal state gray) draws normal states grey and colors only abnormal ones.
Two different sourcesConflict color (recommended)For sources that may run together (a Parallel level): Color of the priority source or Two colors, dashed.
Secured supplyDo not markA section that stays fed after losing one switch or transformer (ring, parallel transformers): Double width or Brighter tone.
De-energized coloronOff: de-energized sections keep their design color.
Join warningonShow a badge on a switch whose closing would join two networks.

Appearance below sets the default line widths and labels of all electrical objects; a value set on an object wins. State colors cannot be changed per object: a color must mean the same on every screen.

2. Set the voltage levels​

Under Voltage levels, each row has a color, a name, AC or DC, the nominal voltage Un, Dashed, Parallel and three thresholds for measurements.

Voltage levels table with 154 kV, 34.5 kV and 0.4 kV, each with AC, Parallel and the Dead, Live and Hyst. thresholds in % Un.

A new project has six levels: 154 kV, 34.5 kV and 0.4 kV (AC), a 1000 V DC level for BESS and PV and a 750 V DC traction level (both DC, parallel), and a 27.5 kV AC railway level.

  • Parallel: sources of this level may meet without a conflict, for example DC rectifiers on a catenary. On by default for DC and off for AC, because paralleling two AC networks needs synchronisation. When both levels have an Un, a different nominal voltage, or AC meeting DC, is a conflict.
  • Un empty: no voltage mix check and no % Un thresholds for this level.
  • Add level adds a row; deleting a level moves its sources to the first level. The last level cannot be deleted. After a change, a round arrow button (Reset to default levels) returns to the default table.

The thresholds decide what a voltage measurement means. Each is one number in % Un or V:

ThresholdDefaultMeaning
Dead <AC 10 % Un, DC 20 VBelow: no voltage.
Live >70 % UnAbove: voltage present. Between the two is residual voltage, which does not count as energized.
Hyst.2 % UnStops flickering around a threshold.

Below the table:

SettingDefaultMeaning
Section colorFrom level (recommended)From source draws each source in its own color instead of its level's color.
Communication-lost viewLast known position (recommended)Default view of a switch without communication; see step 5.
Mismatch delay (s)5How long topology and measurement may disagree before the mismatch is shown, 0–60.
Blink rate (Hz)10.1–3. 3 Hz is the photosensitivity limit.

3. Set the sources​

Source table (upper row has priority) lists the networks. Each row has a color, a name, its voltage level and Dashed; the upper row wins when two sources reach one section. Two networks of the same level, for example the grid and a generator at 34.5 kV, need two sources: when they meet, YTCC shows a conflict. Add source adds a row.

Add level, Section color, Communication-lost view, Mismatch delay and Blink rate, and the source table with the user sources and the system states Earth fault, Short circuit, Energized, Earthed and Uncertain with their Blink options.

The system states at the end of the table cannot be deleted; set their color and Blink there:

StateDefault
Earth faultAmber, blinking
Short circuitRed, blinking
Energized (measured)Teal
EarthedYellow, dashed
UncertainGrey, dashed
De-energizedGrey
No communicationPink, steady

4. Choose the source of each source symbol​

Select a source symbol (grid supply, generator, PV…) and choose its Source in PROPERTIES. For a transformer or a converter, Source is the source of the lower side, Reverse feed source the source of the upper side when it is fed from below (empty: no energy upwards), and Third winding source the third winding of a three-winding transformer.

PROPERTIES of the grid supply GRID with Source set to 11 · 34.5 kV under ELECTRICAL.

5. Choose the communication lost view​

Communication-lost view sets how a switch without communication is drawn by default: Last known position (recommended) or Unknown (grey ?).

The Communication-lost view setting with Last known position (recommended) under the voltage levels.

On the run screen, while a symbol of the page has lost communication, a button on the control rail shows the current view in its tooltip, Showing last known values or Position hidden while communication is lost; clicking it switches. The choice is kept for each user and page.

Result​

The diagram shows the new colors at once in the editor. Run the project to see them with live values.