Symbol catalogue

The Electrification symbol list contains 78 symbols in 8 categories. The role decides how a symbol behaves in the network: whether it switches, transforms, feeds, consumes or only shows information. Indicator symbols have no terminals and do not take part in the network; bind their signals to the busbar or VT they belong to. For your own symbols, see User-defined electrical symbols.

The ANSI and IEC 61850 columns show the usual designations and are also searchable in the symbol list.

Switching & cells​

SymbolIdRoleANSIIEC 61850
Circuit breakercbSwitch52XCBR + CSWI
Draw-out circuit breaker (truck)cbdSwitch52 (draw-out)XCBR + CSWI (position: GGIO / Pos)
Disconnector (isolator)dsSwitch89XSWI + CSWI + CILO (interlock)
Load break switchlbsSwitch89 (load break) / LBSXSWI
Switch-fusefswSwitchFU + 89XSWI
3-position switch (RMU: open-closed-earthed)ts33-position switch89 / 89EXSWI (3 positions)
Earthing switchesEarthing89E / 89GXSWI (earthing)
Auto-recloserrecSwitch79 (+52)RREC + XCBR
Fuse (HRC)fuFuseFU— (with XSWI)
ContactorconSwitch42XSWI / CSWI
Ring main unit (RMU) – 2 ring + 1 transformer feederrmuRMU89 + 89E · FUXSWI ×3 + CILO

Transformers, reactors & resistors​

SymbolIdRoleANSIIEC 61850
Power transformer (2-winding + OLTC)tr2Transformer87T · 49 · 63 · 90 (OLTC)YPTR + YLTC (+ ATCC)
Three-winding transformertr3Transformer87T · 49 · 63YPTR (3 windings) + YLTC
AutotransformeratrTransformer87T · 49 · 63YPTR (+YLTC)
Distribution transformer (Dyn11)dynTransformer49 · 63 · 87TYPTR
Rectifier / traction transformer (12-pulse)rtrTransformer49 · 63 · 87T · 50/51YPTR
Line / shunt reactorreacSeries element87 · 49ZREA
Neutral grounding resistor (NGR)ngrShunt51N / 51G · 59NZREA/ZRES (neutral) · PTOC
Petersen coil (arc suppression)petShunt64 · 59N · 51NYEFN
Zigzag earthing transformerzzShunt51N · 64YPTR (earthing)

Measurement, protection & sensors​

SymbolIdRoleANSIIEC 61850
Current transformer (CT)ctSeries elementCTTCTR
Voltage transformer (VT / PT)vtShuntVT / PTTVTR
Capacitive voltage transformer (CVT)cvtShuntCVT / CCVTTVTR
Multifunction protection relay (IED)iedIndicator (not in the network)50/51 · 67N · 87 · 21 · 27/59 · 81PTOC · PDIF · PDIS · PTUV/PTOV · PFRC
SynchrochecksynIndicator (not in the network)25RSYN (CSYN: synchroniser)
Power meter / PMUmtrIndicator (not in the network)M (measurement)MMXU · MMTR · MHAI · MSQI
Surge arrestersaShuntSAZSAR
Buchholz / gas-pressure relaybucIndicator (not in the network)63SPTR (transformer monitoring)
Temperature indicator (winding / oil)tmpIndicator (not in the network)49STMP
Arc flash relayarcIndicator (not in the network)AFD (vendor specific)SARC
Flood sensorfloodIndicator (not in the network)—GGIO (generic I/O)
Fire detectorfireIndicator (not in the network)—GGIO
Door / intrusion contactdoorIndicator (not in the network)—GGIO
Energy meter (kWh / tariff meter)kwhSeries element— (metering: not 32/55, a meter)MMTR (+ MMXU)

Power electronics & storage​

SymbolIdRoleANSIIEC 61850
Inverter (DC/AC, PV)invConverter—ZINV
Bidirectional PCS (BESS converter)pcsConverter—ZCON / ZINV
Rectifier (AC/DC)rectConverter—ZRCT
DC/DC converterdcdcConverter—ZCON
Variable frequency drive (VFD)vfdConverter—ZCON (+ZMOT)
Automatic transfer switch (ATS)atsTransfer (ATS)83XSWI (+ CSWI)
Harmonic filter / detuned capacitorsfShunt—ZCAP + ZREA
Capacitor bank (reactive power)capShunt—ZCAP
STATCOM / SVCstcShunt—ZCON (STATCOM) · ZTCR (SVC)
DC fast EV chargerevcLoad—IEC 61851 / ISO 15118 (IEC 61850-90-8 EV)
Battery bank / BESSbatSource—ZBAT (+ ZBTC charging)

Generation & load​

SymbolIdRoleANSIIEC 61850
Synchronous generatorgenSource—ZGEN
MV induction motormotLoad—ZMOT
PV arraypvSource—DPVA · DPVC (IEC 61850-7-420)
Wind turbinewtSource—WTUR · WROT · WGEN (IEC 61400-25)
Hydro turbine-generatorhydSource—ZGEN + IEC 61850-7-410 (hydro)
LoadldLoad—— (measurement: MMXU)
Grid supply (equivalent source)srcSource27 / 59 / 81ZLIN / ZAXN (source) · MMXU

Lines, busbars & cables​

SymbolIdRoleANSIIEC 61850
BusbarbusBusbar87B (busbar differential)— (topology) · measurement with TVTR
Double busbar (Bus-1 / Bus-2)bus2Busbar87B— · CILO (busbar selection interlock)
Overhead line / towerohLoad21 · 67 · 87L · 79ZLIN
Underground cable (XLPE)cabSeries element51 · 87LZCAB
Cable terminationcteSeries element—ZCAB · SPDC (partial discharge)
Line trap (wave trap)ltSeries element——
Outgoing feeder (arrow)fdrLoad——
JunctionjnJunction——
Crossover (not connected)xoCrossover——
Off-page / voltage label (LV-MV)offOff-page connector——

Rail traction​

SymbolIdRoleANSIIEC 61850
DC high-speed circuit breaker (HSCB)hscbSwitch72 (DC breaker) · 76 (DC overcurrent)XCBR (DC) + CSWI
Catenary / overhead contact line (OCS)catBusbar—ZLIN
Third rail + running railtrdBusbar—ZLIN
Pantograph / vehicle collectorpanLoad——
Catenary sectioning switchsswSwitch89XSWI + CSWI
Neutral section / section insulatorinsInsulator——
Voltage limiting device (VLD)vldShunt64 (earth) / EN 50122-1 VLDXSWI / ZSAR (related)

Control & auxiliary​

SymbolIdRoleANSIIEC 61850
RTU / field gatewayrtuIndicator (not in the network)—LLN0 / LPHD (physical device)
UPS (uninterruptible power supply)upsIndicator (not in the network)—ZRCT + ZBAT + ZINV
110 V DC rectifier (charger)redIndicator (not in the network)—ZRCT + ZBTC
Local / remote selector (L/R)lrIndicator (not in the network)43 (manual transfer)CSWI.Loc / LLN0.Loc
Tag-out / locktagIndicator (not in the network)—— (SCADA blocking tag)
Alarm tile (annunciator)annIndicator (not in the network)30 (annunciator)GAPC / alarm list
Measurement box (LCD telemetry)mboxIndicator (not in the network)—MMXU / MMTR (value + quality)
Uncertain voltage / data warningwarnIndicator (not in the network)—Quality = invalid / questionable
Voltage conflictconfIndicator (not in the network)25 (synchronism) · 78 · 81RSYN / alarm