Palette: SCADA › Alarm band. Type in the page file: alarm-band. 14 properties.
Common groups: General, Position, Size; see Common properties.
Appearance
| Property | Field | Values | Default | Bindable | Notes |
|---|
| Font | fontSize | Number | 12 | Yes | |
| Max. unacknowledged alarms | maxRows | Number | 50 | Yes | Maximum unacknowledged alarms requested from the server (default 50, max 200); the band shows two rows, the rest scrolls |
Counters
| Property | Field | Values | Default | Bindable | Notes |
|---|
| High counter: lowest priority | highMinPriority | Medium, High, Critical | High | — | This priority and above count as "High" (default High: high + critical) |
| Medium counter: lowest priority | mediumMinPriority | Low, Medium, High | Medium | — | Priorities from this one up to the "High" threshold count as "Medium" (default Medium) |
Alarm scope
| Property | Field | Values | Default | Bindable | Notes |
|---|
| Areas | areas | Areas | None | — | |
| Path patterns | pathPatterns | Signal path patterns | None | — | |
Links
| Property | Field | Values | Default | Bindable | Notes |
|---|
| Event list page | eventPage | Page | — | — | |
| Alarm list page | alarmPage | Page | — | — | |
Units
| Property | Field | Values | Default | Bindable | Notes |
|---|
| Units | units | Units | None | — | |