Skip to main content

Valve

Palette: SCADA › Valve. Type in the page file: valve. 54 properties.

Common groups: General, Position, Size, Transform, Animation, Shadow, Glow; see Common properties.

Appearance​

PropertyFieldValuesDefaultBindableNotes
AppearancevariantGate valve, Globe valve, Ball valve, Butterfly valve, Check valve, Three-way valve, Control valve (pneumatic), Motor operated valve, Solenoid valve, Hand operated valve, Piston-actuated valve, Plug valve, Diaphragm valve, Needle valve, Angle valve, Angle control valve, Safety relief valve (PSV), Motorized damperGate valve—
BodybodyGate, Globe, Ball, Butterfly, Check valve, Three-way, Plug, Diaphragm, Needle, Corner, Safety relief valve (PSV), DamperGate—
ActuatoractuatorNone, Handwheel, Pneumatic diaphragm, Pneumatic / hydraulic piston, Motorized, SolenoidNone—Shown depending on the object
Fail positionfailPositionNone, FO — fail open, FC — fail closed, FL — fail last (locked), FI — fail indeterminateNone—Shown depending on the object. ISA-5.1: the position the valve goes to on loss of air / power; written next to the actuator
ColorcolorColor#374151Yes
BackgroundbgColorColor#E5E7EBYes
Body when openopenColorColor#4B5563Yes
Fault coloralarmColorColor#DC2626Yes
Appearance styleappearanceProject default, ISA-101 (simple), Mimic (realistic)Project default—

State​

PropertyFieldValuesDefaultBindableNotes
FeedbackfeedbackSingle (open), Double (open + closed), Opening (%)Single (open)—
Open (ZSO)openFbOn / offOffYesShown when Feedback is Single (open) or Double (open + closed)
Closed (ZSC)closedFbOn / offOffYesShown when Feedback is Double (open + closed)
Opening (%)openingNumber0YesShown when Feedback is Opening (%)
Show openingshowOpeningOn / offOff—
Demanded opening (%)setpointNumber—YesShown when Feedback is Opening (%). Control valve output (setpoint). When it differs from the opening by more than the deadband: transition; when the travel time runs out: discrepancy; marker on the position bar
Deadband (%)deadbandNumber2—Shown when Feedback is Opening (%)
Position barpositionBarOn / offOff—Shown when Feedback is Opening (%). With "Show opening" on, a position bar under the text; if the demanded opening is bound, a marker on the bar
FaultfaultOn / offOffYes
Mode lettermodeTextText—Yes
Device diagnostics (NE 107)diagText—Yes

Operation​

PropertyFieldValuesDefaultBindableNotes
CommandcommandOn / offOffYesShown when Feedback is Single (open) or Double (open + closed). Maintained command signal (run / open request; not a pulse command). While it differs from the feedback: transition (half fill); when the travel time runs out: discrepancy (alarm color + badge)
Travel time (s)travelTimeNumber30—If the command is not fulfilled within this time: discrepancy. Empty: motor / pump 10 s, valve 30 s
Interlock (not permitted)interlockOn / offOffYesPadlock mark (colorless): answers on screen why the equipment is not running
Out of service / maintenanceoutOfServiceOn / offOffYes
Simulation (SIM)simulatedOn / offOffYes

Alarm​

PropertyFieldValuesDefaultBindableNotes
Alarm priorityalarmPriorityNumber0Yes0 none, 1 highest … 4. Shape + number per priority, same as the alarm list: 1 circle, 2 triangle, 3 square, 4 diamond
Unacknowledged (blinks)alarmUnackedOn / offOffYes
Shelved / suppressedalarmShelvedOn / offOffYesGrey dashed "S": the alarm was silenced by the operator and stays visible on screen