Pump / Fan
Palette: SCADA › Pump / Fan. Type in the page file: pump. 48 properties.
Common groups: General, Position, Size, Transform, Animation, Shadow, Glow; see Common properties.
Appearance
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Appearance | variant | Centrifugal pump, Pump (general), Gear pump, Progressive cavity pump, Reciprocating pump, Diaphragm (metering) pump, Peristaltic pump, Submersible pump, Vacuum pump, Compressor, Reciprocating compressor, Screw compressor, Fan, Axial (duct) fan, Blower, Agitator, Rotary feeder (airlock) | Centrifugal pump | — | |
| Color | color | Color | #374151 | Yes | |
| Background | bgColor | Color | #E5E7EB | Yes | |
| Body when running | runColor | Color | #4B5563 | Yes | |
| Fault color | alarmColor | Color | #DC2626 | Yes | |
| Appearance style | appearance | Project default, ISA-101 (simple), Mimic (realistic) | Project default | — | |
| Paint color (mimic) | paintColor | Color | #2F6A9A | Yes |
State
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Running | running | On / off | Off | Yes | |
| Fault | fault | On / off | Off | Yes | |
| Mode letter | modeText | Text | — | Yes | |
| Device diagnostics (NE 107) | diag | Text | — | Yes | |
| Speed | speed | Number | — | Yes | Drive speed (bound to a signal); written under the symbol while "Show speed" is on |
| Speed unit | speedUnit | Text | % | — | |
| Show speed | showSpeed | On / off | Off | — |
Operation
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Command | command | On / off | Off | Yes | Maintained command signal (run / open request; not a pulse command). While it differs from the feedback: transition (half fill); when the travel time runs out: discrepancy (alarm color + badge) |
| Travel time (s) | travelTime | Number | 10 | — | If the command is not fulfilled within this time: discrepancy. Empty: motor / pump 10 s, valve 30 s |
| Interlock (not permitted) | interlock | On / off | Off | Yes | Padlock mark (colorless): answers on screen why the equipment is not running |
| Out of service / maintenance | outOfService | On / off | Off | Yes | |
| Simulation (SIM) | simulated | On / off | Off | Yes |
Alarm
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Alarm priority | alarmPriority | Number | 0 | Yes | 0 none, 1 highest … 4. Shape + number per priority, same as the alarm list: 1 circle, 2 triangle, 3 square, 4 diamond |
| Unacknowledged (blinks) | alarmUnacked | On / off | Off | Yes | |
| Shelved / suppressed | alarmShelved | On / off | Off | Yes | Grey dashed "S": the alarm was silenced by the operator and stays visible on screen |