Electrical symbol
Palette: SCADA › Electrification. Type in the page file: elec. 67 properties.
Common groups: General, Position, Size, Transform, Animation, Shadow, Glow; see Common properties.
Appearance
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Symbol | symbol | List (78 entries) | Circuit breaker | — | |
| Variant | variant | Symbol variant | — | — | Shown when Symbol is user:<id>. Empty: the project or catalogue value |
| Line width | lineWidth | Number | — | — | Shown when Symbol is Busbar or Double busbar (Bus-1 / Bus-2) or Catenary / overhead contact line (OCS) or Third rail + running rail. Empty: the project or catalogue value |
| Line width (×) | strokeScale | Number | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or 3-position switch (RMU: open-closed-earthed) or Earthing switch or Auto-recloser or Fuse (HRC) or Contactor or Power transformer (2-winding + OLTC) or Three-winding transformer or Autotransformer or Distribution transformer (Dyn11) or Rectifier / traction transformer (12-pulse) or Line / shunt reactor or Neutral grounding resistor (NGR) or Petersen coil (arc suppression) or Zigzag earthing transformer or Current transformer (CT) or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Multifunction protection relay (IED) or Synchrocheck or Power meter / PMU or Surge arrester or Buchholz / gas-pressure relay or Temperature indicator (winding / oil) or Arc flash relay or Flood sensor or Fire detector or Door / intrusion contact or Inverter (DC/AC, PV) or Bidirectional PCS (BESS converter) or Rectifier (AC/DC) or DC/DC converter or Variable frequency drive (VFD) or Automatic transfer switch (ATS) or Harmonic filter / detuned capacitor or Capacitor bank (reactive power) or STATCOM / SVC or DC fast EV charger or Battery bank / BESS or Synchronous generator or MV induction motor or PV array or Wind turbine or Hydro turbine-generator or Load or Grid supply (equivalent source) or Overhead line / tower or Underground cable (XLPE) or Cable termination or Line trap (wave trap) or Outgoing feeder (arrow) or Junction or Crossover (not connected) or Off-page / voltage label (LV-MV) or DC high-speed circuit breaker (HSCB) or Pantograph / vehicle collector or Catenary sectioning switch or Neutral section / section insulator or Voltage limiting device (VLD) or RTU / field gateway or UPS (uninterruptible power supply) or 110 V DC rectifier (charger) or Local / remote selector (L/R) or Tag-out / lock or Alarm tile (annunciator) or Ring main unit (RMU) – 2 ring + 1 transformer feeder or Energy meter (kWh / tariff meter) or Measurement box (LCD telemetry) or Uncertain voltage / data warning or Voltage conflict. Empty: the project or catalogue value |
| Label | label | Text | — | — | |
| Show label | labelHidden | On / off | On | — | |
| Label position | labelPosition | Top, Lower, Left, Right | — | — | Empty: the project or catalogue value |
| Label font family | labelFontFamily | Font | — | — | Empty: the project or catalogue value |
| Label size | labelFontSize | Number | — | — | Empty: the project or catalogue value |
| Label weight | labelFontWeight | Normal, Semibold, Bold | — | — | Empty: the project or catalogue value |
| Label color | labelColor | Color | — | — | Empty: the project or catalogue value |
Additional information
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Additional signals | extra | Additional signals | — | — | Shown when Symbol is user:<id> |
| Symbol parameters | symParams | Symbol parameters | — | — | Shown when Symbol is user:<id> |
Electrical
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Color source (page/object) | colorSource | Text | — | — | Empty: colored from its own connections. Otherwise <page id>/<object id> of a device, for example overview/cb_12: the object shows the color that device has on its own page |
| Link name | linkName | Text | — | — | Shown when Symbol is Off-page / voltage label (LV-MV) |
| Source | source | Source | — | — | Shown when Symbol is Power transformer (2-winding + OLTC) or Three-winding transformer or Autotransformer or Distribution transformer (Dyn11) or Rectifier / traction transformer (12-pulse) or Inverter (DC/AC, PV) or Bidirectional PCS (BESS converter) or Rectifier (AC/DC) or DC/DC converter or Variable frequency drive (VFD) or Battery bank / BESS or Synchronous generator or PV array or Wind turbine or Hydro turbine-generator or Grid supply (equivalent source) |
| Third winding source | source2 | Source | — | — | Shown when Symbol is Three-winding transformer or Autotransformer or Rectifier / traction transformer (12-pulse) |
| Reverse feed source | reverseSource | Source | — | — | Shown when Symbol is Power transformer (2-winding + OLTC) or Three-winding transformer or Autotransformer or Distribution transformer (Dyn11) or Rectifier / traction transformer (12-pulse) or Inverter (DC/AC, PV) or Bidirectional PCS (BESS converter) or DC/DC converter or Rectifier (AC/DC) or Variable frequency drive (VFD) |
| Consumer criticality | criticality | Important, Critical | — | — | Shown when Symbol is DC fast EV charger or MV induction motor or Load or Overhead line / tower or Outgoing feeder (arrow) or Pantograph / vehicle collector. Alarm priority when the consumer is not supplied: Normal → low, Important (e.g. pumping station) → high, Critical (e.g. signalling supply, hospital) → critical. An outage zone takes the priority of its most critical consumer. Empty: the project or catalogue value |
State
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Position (double point) | position | Number | 2 | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or 3-position switch (RMU: open-closed-earthed) or Earthing switch or Auto-recloser or Contactor or Automatic transfer switch (ATS) or DC high-speed circuit breaker (HSCB) or Catenary sectioning switch |
| Second position (double point) | position2 | Number | 1 | Yes | Shown when Symbol is 3-position switch (RMU: open-closed-earthed) or Automatic transfer switch (ATS) |
| Trip (protection operated) | tripped | On / off | Off | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Auto-recloser or DC high-speed circuit breaker (HSCB) |
| Earth fault (51N / 67N) | faultEarth | On / off | Off | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Auto-recloser or DC high-speed circuit breaker (HSCB) |
| Short circuit (50 / 51 / 21) | faultShort | On / off | Off | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Auto-recloser or DC high-speed circuit breaker (HSCB) |
| In test / withdrawn position | racked | On / off | Off | Yes | Shown when Symbol is Draw-out circuit breaker (truck) |
| Fuse blown | fuseBlown | On / off | Off | Yes | Shown when Symbol is Switch-fuse or Fuse (HRC) |
| Voltage present | voltagePresent | On / off | On | Yes | Shown when Symbol is Battery bank / BESS or Synchronous generator or PV array or Wind turbine or Hydro turbine-generator or Grid supply (equivalent source) |
| Local control (L) | local | On / off | Off | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or 3-position switch (RMU: open-closed-earthed) or Earthing switch or Auto-recloser or Contactor or Automatic transfer switch (ATS) or DC high-speed circuit breaker (HSCB) or Catenary sectioning switch |
Control
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Command signal | command | Signal | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or 3-position switch (RMU: open-closed-earthed) or Earthing switch or Auto-recloser or Contactor or Automatic transfer switch (ATS) or DC high-speed circuit breaker (HSCB) or Catenary sectioning switch |
| Second position command signal | command2 | Signal | — | — | Shown when Symbol is 3-position switch (RMU: open-closed-earthed) or Automatic transfer switch (ATS) |
Measurement
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Measurement input | measureInput | Analogue voltage (V), Digital voltage present / absent, Analogue + digital | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch. Empty: the project or catalogue value |
| Voltage measurement (V) | voltage | Number | — | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch |
| Voltage present (digital) | voltageDetected | On / off | Off | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch |
| VT healthy (fuse / MCB) | vtHealthy | On / off | On | Yes | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch |
| Measurement level | measureLevel | Voltage level | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch |
| Measured terminal | voltageTerminal | Top (t), Bottom (b) | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or DC high-speed circuit breaker (HSCB) or Auto-recloser or Load break switch or Contactor or Switch-fuse or Catenary sectioning switch or Disconnector (isolator) or Current transformer (CT) or Overhead line / tower or Underground cable (XLPE). Empty: the project or catalogue value |
| Measurement thresholds | thresholds | Thresholds | — | — | Shown when Symbol is Circuit breaker or Draw-out circuit breaker (truck) or Disconnector (isolator) or Load break switch or Switch-fuse or Auto-recloser or Contactor or Voltage transformer (VT / PT) or Capacitive voltage transformer (CVT) or Busbar or Double busbar (Bus-1 / Bus-2) or Overhead line / tower or Underground cable (XLPE) or Outgoing feeder (arrow) or DC high-speed circuit breaker (HSCB) or Catenary / overhead contact line (OCS) or Third rail + running rail or Catenary sectioning switch |
Measurement
| Property | Field | Values | Default | Bindable | Notes |
|---|---|---|---|---|---|
| Measurement label | measureLabel | Text | P | Yes | Shown when Symbol is Measurement box (LCD telemetry) |
| Value | value | Number | 0 | Yes | Shown when Symbol is Measurement box (LCD telemetry) |
| Unit | unit | Text | MW | Yes | Shown when Symbol is Measurement box (LCD telemetry) |
| Decimal | decimals | Number | 1 | — | Shown when Symbol is Measurement box (LCD telemetry) |