Skip to main content

Motor

Palette: SCADA › Motor. Type in the page file: motor. 50 properties.

Common groups: General, Position, Size, Transform, Animation, Shadow, Glow; see Common properties.

Appearance​

PropertyFieldValuesDefaultBindableNotes
AppearancevariantSimple (ISA-101), IEC 60617, IEC 60617 single-phase (1~), IEC 60617 DC (=), Generator (G 3~), Gear motor, Servomotor, Motor with drive (VFD), Explosion-proof motor (Ex), Flange motor (B5), Vertical motor (V1), Bladed, ClassicSimple (ISA-101)—
Symbol lettersymbolTextTextMYes
ColorcolorColor#374151Yes
BackgroundbgColorColor#E5E7EBYes
Body when runningrunColorColor#4B5563YesShown depending on the object
Fault coloralarmColorColor—Yes
Appearance styleappearanceProject default, ISA-101 (simple), Mimic (realistic)Project default—
Paint color (mimic)paintColorColor#2F6A9AYes

State​

PropertyFieldValuesDefaultBindableNotes
RunningrunningOn / offOffYes
Speed (rpm)rpmNumber1500YesRotation speed only; 1500 when there is no value (does not affect the running state)
FaultfaultOn / offOffYes
Mode lettermodeTextText—Yes
Device diagnostics (NE 107)diagText—Yes
SpeedspeedNumber—YesDrive speed (bound to a signal); written under the symbol while "Show speed" is on
Speed unitspeedUnitText%—
Show speedshowSpeedOn / offOff—

Operation​

PropertyFieldValuesDefaultBindableNotes
CommandcommandOn / offOffYesMaintained command signal (run / open request; not a pulse command). While it differs from the feedback: transition (half fill); when the travel time runs out: discrepancy (alarm color + badge)
Travel time (s)travelTimeNumber10—If the command is not fulfilled within this time: discrepancy. Empty: motor / pump 10 s, valve 30 s
Interlock (not permitted)interlockOn / offOffYesPadlock mark (colorless): answers on screen why the equipment is not running
Out of service / maintenanceoutOfServiceOn / offOffYes
Simulation (SIM)simulatedOn / offOffYes

Alarm​

PropertyFieldValuesDefaultBindableNotes
Alarm priorityalarmPriorityNumber0Yes0 none, 1 highest … 4. Shape + number per priority, same as the alarm list: 1 circle, 2 triangle, 3 square, 4 diamond
Unacknowledged (blinks)alarmUnackedOn / offOffYes
Shelved / suppressedalarmShelvedOn / offOffYesGrey dashed "S": the alarm was silenced by the operator and stays visible on screen